All Inquiries
Project: BIDDER INQUIRY D/B DISA FUEL TANK     Review: W9127820SFHZ0001 (00001)
(sorted by CommentID )
Displaying 10 inquiries.
Id Discipline Sheet Detail Spec
8799039 Civil G-101  Note 2  n/a 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

General note 2 states, "THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY UNKNOWN UNDERGROUND UTILITIES." This is an unreasonable expectation as the contractor(s) bidding do not have knowledge of any utilities other than what has been provided in the conceptual drawings. Suggestion would be to establish an allowance so that all contractors bid the same way or remove this note/requirement from the contract documents.

  On: Aug 28 2020.
  Government Response. .   Design is correct as shown. Please bid in compliance with information currently provided in the plans and specs. Plans were provided for information only. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8801873 Electrical     Section 01 10 10 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Paragraph 8.2 of Section 01 10 10states to "Provide lightning protection for all outdoor equipment." Is this requirement for only new work equipment or is there also new LP work required for existing equipment?

  On: Aug 31 2020.
  Government Response. .   Design is correct as shown. Please bid in compliance with information currently provided in the plans and specs. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8801876 Electrical     Section 01 10 10 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Please confirm that Lightning Protection will entail grounding of equipment to the existing grounding system and no overhead (catenary) lightning protection system is required.

  On: Aug 31 2020.
  Government Response. .   Design is correct as shown. Please bid in compliance with information currently provided in the plans and specs. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8808252 Equipment M-100     
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Can pumps be sized based on best engineering practice or is the 150 GPM requirement fixed? The stated requirement for 150 GPM fuel transfer pump flow appears to be too high for this application. Each 2 MW generator will consume about 140 gallons per hour for a total of 560 gallons per hour for four generators. Industry practice is to apply a safety factor of 3-4 times generator consumption, so the pumps should be sized for 1,600 to 2,100 gallons per hour. Filling generator day tanks at 150 gallons per minute (9,000 GPH) would present safety and operational problems including: foaming of the oil that could cause float switches and level sensors to malfunction and the engine fuel pump to lose prime, and potential overfilling of tanks if tank fill valves do not close fast enough.

  On: Sep 02 2020.
  Government Response. .   The answer was issued in Amendment No. 0001, Section 01010, Paragraph 7.2.1 On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8809200 Project Management     Section 01 10 12 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Paragraph 4 of Section 01 10 12 references Eglin AFB, FL. Please provide the correct location.

  On: Sep 03 2020.
  Government Response. .   The answer was issued in Amendment No. 0001, Section 01 10 12, Paragraph 4. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8809209 Project Management     Section 01 10 12 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Paragraph 2.4 of Section 01 10 12 indicates fast track and a 100% unreviewed design submittal. However, Paragraphs 6.1 and 6.2 mention 65% and final design submittals. Which is correct?

  On: Sep 03 2020.
  Government Response. .   The answer was issued in Amendment No. 0001, Section 01 10 12, Paragraph 2.4. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8809215 Project Management     Section 01 10 12 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Paragraph 4 of Section 01 10 12 mentions a 14 day review time. However, Paragraph 10 mentions a 21 day review time. Which is correct?

  On: Sep 03 2020.
  Government Response. .   The answer was issued in Amendment No. 0001, Section 01 10 12, Paragraph 4. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8809218 Project Management     Section 01 10 10 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Paragraph 8.3.1 of Section 01 10 10 references a roof top unit requirement. There is no other information regarding a roof top unit. Please clarify.

  On: Sep 03 2020.
  Government Response. .   The answer was issued in Amendment No. 0001, Section 01 10 12, Paragraph 8.3.1. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8825961 Equipment     01 10 10 7.8 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Do the existing day tanks at each generator already have any of the following:
- Flow control manifolds;
- Emergency high and low switches (in addition to high and low);
- Flow limiters;
- Bypass valves for hand filling;
- Flow switches;
- Automated shutoff valves

  On: Sep 14 2020.
  Government Response. .   Design is correct as shown. Please bid in compliance with information currently provided in the plans and specs. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.
8825980 Equipment     01 10 10 1.0 
Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)

Project objectives call for providing the fuel system for four existing generators. A satellite view of the facility seems to indicate that only three of the generators are currently existing with a space for the fourth, but the view may not be current. Is the fourth generator existing; and if not, to what extent are piping and controls to be provided to the empty generator location?

  On: Sep 14 2020.
  Government Response. .   Design is correct as shown. Please bid in compliance with information currently provided in the plans and specs. On: Sep 23 2020
  Current Request Status: Request Closed
Information for this report is procurement sensitive.